Refrigerants explained
From ammonia and CFCs to propane and CO₂: what each refrigerant family is, how hard it hits the climate and the ozone layer, why the industry keeps changing, and what replaced what.
Start here
Three numbers that tell you most of the story
A refrigerant is the fluid that carries heat around inside your air conditioner, fridge or cool room. Each one is described by how much it warms the climate, whether it harms the ozone layer, and how safe it is to work with.
- GWP
Global warming potential
How much a gas warms the planet compared with the same mass of carbon dioxide over 100 years. A gas with a GWP of 2,088, like R410A, has the same warming effect as 2,088 times as much CO₂[1].
- ODP
Ozone depletion potential
How much a gas damages the ozone layer. R11 is the reference at 1.0 [11]. Gases with no chlorine or bromine, such as HFCs, HFOs and the natural refrigerants, do not deplete ozone.
- A1 to B2L
Safety class
A letter for toxicity (A lower, B higher) and a number for flammability: 1 no flame spread, 2L lower flammability, 2 flammable, 3 higher flammability [3].
Which GWP numbers do we use? The 100-year values from the IPCC Fourth Assessment Report (AR4), because that is what Australia’s Ozone Protection and Synthetic Greenhouse Gas Management Act and the Montreal Protocol use for the HFC phase-down [3]. Later IPCC reports give slightly different numbers, so you may see other figures elsewhere. We show AR5 for single gases as an option in the table.
The main families
CFCs, HCFCs, HFCs, HFOs and natural refrigerants
Refrigerants are grouped by what they are made of. The family tells you a lot about ozone, climate and handling.
- CFC
CFCs
Chlorofluorocarbons
Carbon, chlorine and fluorine. They were a huge step forward when they arrived: stable, not toxic and not flammable. That same stability is the problem. They survive long enough to reach the upper atmosphere, where sunlight frees the chlorine that destroys ozone. They are also extremely strong greenhouse gases.
- R11
- R12
- R502 (a blend that contains CFC-115)
- HCFC
HCFCs
Hydrochlorofluorocarbons
CFCs with hydrogen added. The hydrogen lets them break down lower in the atmosphere, so they damage ozone much less, but not zero. They became the transition gas of the 1990s. R22 is the one you will still meet in older air conditioners and cool rooms.
- R22
- HFC
HFCs
Hydrofluorocarbons
No chlorine, so no ozone damage. They replaced CFCs and HCFCs from the 1990s. The catch is climate: they are strong greenhouse gases. Some are single gases (R134a, R32) and some are blends (R404A, R407C, R410A, R507A).
- R134a
- R404A
- R407C
- R410A
- R32
- R507A
- HFO / blend
HFOs and HFC/HFO blends
Hydrofluoro-olefins
HFOs have a carbon double bond, so they break down in the atmosphere within weeks, which is why their GWP is so low. Pure HFOs (R1234yf, R1234ze) are mildly flammable. Many blends mix an HFO with HFCs to get the right performance. Those blends (R448A, R449A, R513A, R454B) are lower in GWP than the gases they replace, but lower is not zero.
- R1234yf
- R1234ze(E)
- R448A
- R449A
- R513A
- R454B
- Ozone damage
- None
- Status
- Pure HFOs are not controlled under the Act. Blends that contain an HFC are [4].
- Natural
Natural refrigerants
CO₂ (R744), propane (R290), isobutane (R600a), ammonia (R717)
Substances that occur in nature and were used as refrigerants long before CFCs. They have no ozone impact and a GWP of 5 or less. The trade-off is that each one has a hazard that equipment and training have to manage: propane and isobutane burn, CO₂ runs at very high pressure, and ammonia is toxic.
- R744 (CO₂)
- R290 (propane)
- R600a (isobutane)
- R717 (ammonia)
- Ozone damage
- None
- GWP (AR4)
- CO₂ is the reference at 1. The others are less than 5 [3]
Compare the gases
GWP, ozone impact and safety class
Twenty common refrigerants, side by side. The bar is drawn to scale, so the low-GWP gases really are that small.
| Refrigerant | Family | GWP, 100 years (AR4) | ODP | Safety class | GWP (AR5) | Typically found in |
|---|---|---|---|---|---|---|
| R11CFC-11, trichlorofluoromethane | CFC | 4,750 | 1.0 | A1 | 4,660 | Older centrifugal chillers |
| R12CFC-12, dichlorodifluoromethane | CFC | 10,900 | 1.0 | A1 | 10,200 | Older fridges and car air-con |
| R502Blend: R22 48.8% + R115 51.2% (CFC/HCFC)GWP is the Montreal Protocol (AR4) basis figure, which is the AR4 values of its two gases weighted by composition. ODP likewise. | CFC | 4,657 | 0.334 | A1 | — | Older low-temperature refrigeration |
| R22HCFC-22, chlorodifluoromethane | HCFC | 1,810 | 0.055 | A1 | 1,760 | Older air conditioners and refrigeration |
| R134aHFC-134a, tetrafluoroethane | HFC | 1,430 | 0 | A1 | 1,300 | Car air-con and fridges |
| R404ABlend: R125 44% + R143a 52% + R134a 4% | HFC | 3,922 | 0 | A1 | — | Commercial refrigeration |
| R407CBlend: R32 23% + R125 25% + R134a 52% | HFC | 1,774 | 0 | A1 | — | R22 replacement in air conditioning |
| R410ABlend: R32 50% + R125 50% | HFC | 2,088 | 0 | A1 | — | Split systems and heat pumps |
| R32HFC-32, difluoromethane | HFC | 675 | 0 | A2L | 677 | Newer split systems |
| R507ABlend: R125 50% + R143a 50% | HFC | 3,985 | 0 | A1 | — | Low-temperature refrigeration |
| R448AHFC/HFO blend: R32, R125, R1234yf, R134a, R1234ze | HFC/HFO blend | 1,386 | 0 | A1 | — | Lower-GWP option where R404A was used |
| R449AHFC/HFO blend: R32, R125, R1234yf, R134a | HFC/HFO blend | 1,396 | 0 | A1 | — | Lower-GWP option where R404A was used |
| R513AHFC/HFO blend: R1234yf 56% + R134a 44% | HFC/HFO blend | 629 | 0 | A1 | — | Lower-GWP option where R134a is used |
| R454BHFC/HFO blend: R32 68.9% + R1234yf 31.1% | HFC/HFO blend | 465 | 0 | A2L | — | Lower-GWP blend, mildly flammable |
| R1234yfHFO-1234yf, tetrafluoropropene | HFO | <5 | 0 | A2L | <1 | Car air-con |
| R1234ze(E)HFO-1234ze, tetrafluoropropene | HFO | <5 | 0 | A2L | <1 | On its own, and as an ingredient in blends |
| R290Propane | Natural | <5 | 0 | A3 | — | Small sealed refrigeration equipment |
| R600aIsobutane | Natural | <5 | 0 | A3 | — | Small sealed fridges and freezers |
| R744Carbon dioxide (CO₂) | Natural | 1 | 0 | A1 | 1 | Systems built for very high pressure |
| R717Ammonia (NH₃) | Natural | <5 | 0 | B2L | — | Large industrial plants |
How to read it. GWP is the 100-year value from IPCC AR4 as used by the Australian Government and the Montreal Protocol [1][3][11][12]. “<5” is how the Government lists HFOs, hydrocarbons and ammonia [3]. CO₂ is the reference gas, so its GWP is 1. ODP is shown as 0 for gases with no chlorine or bromine [16].
R502 and blends. R502 is not in the IPCC table. Its GWP (4,657) and ODP (0.334) come from its two component gases, weighted by composition, and match the ASHRAE and UNEP figures [13][16][17]. HFC and HFC/HFO blend GWPs are the Government’s AR4 figures [3].
AR5. The optional AR5 column covers single gases only, from the IPCC Fifth Assessment Report [2]. A dash means there is no AR5 figure for that single gas in the IPCC table, or the gas is a blend.
Safety class comes from the Government’s list [3] and ASHRAE’s tables for the older gases [16]. Equipment designed for one refrigerant must stay on that refrigerant.
The safety classes at a glance
The letter is toxicity (A lower, B higher). The number is flammability. Examples are from the table above, plus R152a.
- A1
Lower toxicity, no flame spread
Examples: R11, R12, R22, R134a, R404A, R410A, R448A, R513A, R744[3][16]
- A2L
Lower toxicity, lower flammability
Examples: R32, R454B, R1234yf, R1234ze(E)[3]
- A2
Lower toxicity, flammable
Examples: R152a (HFC-152a)[3]
- A3
Lower toxicity, higher flammability
Examples: R290, R600a[3]
- B2L
Higher toxicity, lower flammability
- B1
Higher toxicity, no flame spread
Not used for any refrigerant in the table above. The letter B means higher toxicity, as in the classes above [3].
- B2
Higher toxicity, flammable
Not used for any refrigerant in the table above. The letter B means higher toxicity, as in the classes above [3].
- B3
Higher toxicity, higher flammability
Not used for any refrigerant in the table above. The letter B means higher toxicity, as in the classes above [3].
Why the industry keeps moving
First the ozone layer, now the climate
Each change was driven by a real problem with the previous generation. Today the push is towards low and near-zero GWP.
1987 to today
The Montreal Protocol
Agreed on 16 September 1987 and in force from 1 January 1989 [15]. It phased out CFCs (done in developed countries by 1995) and is phasing out HCFCs [6].
Australia’s own limit on new HCFC imports reaches zero in 2030 [7].
2016, in force 2019
The Kigali Amendment
Adopted on 15 October 2016 and in force from 1 January 2019 [14][15]. It phases down HFCs, which have no ozone impact but are strong greenhouse gases. For developed countries that means an 85% reduction by 2036 [6]. UNEP estimates it avoids around 0.4°C of global heating [15].
2018 to 2036
Australia’s HFC phase-down
Run under the Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 and its regulations [20][21]. It caps bulk HFC imports in CO₂-equivalent, started on 1 January 2018 (a year before the Protocol required), and ends at 1.607 million tonnes a year from 2036, 85% below the baseline [4][6].
Australia’s cap on bulk HFC imports
Million tonnes of CO₂-equivalent a year, by two-year quota period [4][21]
- 8.002018–19: 8.000 million tonnes CO₂-equivalent
- 7.252020–21: 7.250 million tonnes CO₂-equivalent
- 6.252022–23: 6.250 million tonnes CO₂-equivalent
- 5.252024–25: 5.250 million tonnes CO₂-equivalent
- 4.252026–27: 4.250 million tonnes CO₂-equivalent
- 3.202028–29: 3.200 million tonnes CO₂-equivalent
- 2.902030–31: 2.900 million tonnes CO₂-equivalent
- 2.652032–33: 2.650 million tonnes CO₂-equivalent
- 2.102034–35: 2.100 million tonnes CO₂-equivalent
- 1.612036 on: 1.607 million tonnes CO₂-equivalent
What the phase-down does and does not mean
- It caps imports of bulk gas (cylinders). It does not cap gas already inside imported equipment [4][5].
- Existing equipment is not affected. Nobody is forced to replace a working system because of the phase-down [4].
- HFCs are phased down, not banned. A residual amount can still be imported from 2036 for uses like servicing [4].
- The cap is counted in CO₂-equivalent, so a kilogram of a high-GWP gas uses up far more of the quota than a kilogram of a low-GWP gas. Industry body Refrigerants Australia expects supply of the high-GWP gases to tighten first [23].
- Government says bans on new equipment could be considered in future, after consultation. Any such ban would apply to new equipment only [4].
The trade-offs of going low or zero GWP
As a refrigerant’s GWP drops, flammability tends to rise [8]. No option is perfect, which is why each has its own rules and training.
- A3
- A1
High pressure: CO₂ (R744)
Not toxic or flammable, but CO₂’s critical point is only about 31°C and 73.8 bar [16]. In hot weather a CO₂ system has to run at very high pressure, so it needs components built for it.
- B2L
Toxic: ammonia (R717)
Higher toxicity and lower flammability. It remains the most popular refrigerant in large industrial systems, such as food and beverage processing and storage [19]. It is not a home or small-business refrigerant.
- Blends
A hundred years of refrigerants
Timeline: from ammonia to low-GWP
Four generations, according to the refrigerant historian J. M. Calm: whatever worked, safety and durability, ozone protection, and now global warming [19].
- 1830s–1920s
Whatever worked
Early refrigerants were whatever was available and worked: ethers, CO₂, ammonia, sulphur dioxide, methyl formate and hydrocarbons. Nearly all were flammable, toxic or both, and accidents were common.[19][18]
- 1922
Propane sold as the “odorless safety refrigerant”
A reminder that natural refrigerants are not new. Propane was being advertised as a refrigerant a century ago.[18]
- 1927
Household fridges go mainstream
The General Electric “Monitor Top” is regarded as the first affordable fridge. Early units used sulphur dioxide, methyl formate, ammonia or methyl chloride, all toxic and flammable.[18]
- 1930–32
CFCs arrive: R12 in 1931, R11 in 1932
Thomas Midgley, Albert Henne and Robert McNary searched for a safer refrigerant and published the work in 1930. Commercial production of R12 began in 1931 and R11 in 1932. Stable, not toxic, not flammable: the CFC era begins.[18][19]
- 1936–1950s
HCFCs: R22 and the blends
R22 was first commercialised in 1936 and became widely used in air conditioning from the late 1950s. From the 1950s, mixtures of CFCs and HCFCs (R502 is one) came into use to suit particular applications.[18][17]
- 1974
Rowland and Molina warn about CFCs
A paper in the journal Nature warns that human-made CFCs are harming the ozone layer.[15]
- 1985
Vienna Convention and the Antarctic ozone hole
The Vienna Convention is adopted, and British Antarctic Survey scientists report the recurring springtime ozone hole.[15][6]
- 1987–89
Montreal Protocol
Adopted on 16 September 1987 and in force from 1 January 1989. It has since been strengthened by amendments and is widely considered the most successful environmental agreement.[15][6]
- Late 1989–1990s
HFCs replace CFCs and HCFCs
The first alternatives were commercialised in late 1989, and within about ten years most ozone-depleting refrigerants had replacements. R134a took over from R12, and blends such as R407C and R410A took over from R22. HFCs have no chlorine, and their GWP was judged “low enough” at the time.[19][18]
- 1991–96
CFC then HCFC phase-outs begin
Phase-out of CFCs begins in 1991 and is complete in developed countries by 1995. The phase-out of HCFCs begins in 1996.[6]
- 2007
HCFC phase-out accelerated
The Montreal Protocol is adjusted to speed up the HCFC phase-out.[15][6]
- 2008–2010s
Climate becomes the driver: HFOs
By 2008 HFOs were a regular topic at industry conferences. R1234yf was developed for car air-con to meet an EU limit of GWP under 150, and the EU’s F-gas rules were the first to regulate HFCs.[18]
- 2016
Kigali Amendment, 15 October
Countries agree to phase down HFCs under the Montreal Protocol. UNEP estimates it avoids around 0.4°C of global heating.[15][14]
- 2018
Australia’s HFC phase-down starts, 1 January
Australia began one year before the Protocol required. The first annual limit on bulk HFC imports was 8.0 million tonnes of CO₂-equivalent.[6][4]
- 2019
Kigali enters into force, 1 January
The Kigali Amendment becomes binding on the countries that have ratified it.[14][15]
- 2020
HCFCs: servicing only
From 1 January 2020, bulk HCFC imported into Australia can only be used to service existing equipment, meaning equipment made or imported before that date.[7]
- 2026–27
HFC limit steps down to 4.25 Mt
The annual limit on bulk HFC imports is now 4.25 million tonnes of CO₂-equivalent, down from 8.0 at the start.[4][21]
- 2030
HCFC import limit reaches zero
Australia’s annual import limit for new HCFCs falls to zero. The HFC limit steps down to 2.9 Mt.[7][4]
- 2036
85% down: 1.607 Mt a year
The phase-down ends at 15% of the baseline, 1.607 million tonnes of CO₂-equivalent a year, and stays there. HFCs are phased down, not banned.[4]
What replaced what
The substitution map
Three families of equipment, read left to right (or top to bottom on a phone). Each box shows the GWP (AR4) and safety class.
Fridges and car air-con
Air conditioning and heat pumps
Commercial refrigeration
- Original
- R502CFC/HCFC blend · Phased outGWP 4,657Class A1
- HFC era
- Lower-GWP options
- Original
How to read this. The first two steps are well documented: R134a replaced R12 in cars, and R407C and R410A replaced R22 [18]. The third step shows the lower-GWP options the industry and government are working towards. Australian industry has pointed to R32 in split systems, R1234yf in car air-con and R448A or R449A in place of R404A in commercial refrigeration [23]. Other options on the map are listed by the Government with their GWP and safety class [3]. R502 was replaced by HFC blends such as R404A and R507A, an azeotrope of R125 and R143a [17][18].
What is next. The direction is lower GWP, using HFOs, blends and natural refrigerants (including a swing back to ammonia, CO₂ and hydrocarbons) [18][19]. Each trades GWP against flammability, pressure or toxicity, and the right choice depends on the equipment.
This is not a swap list. Equipment is designed for one refrigerant. Existing A1 systems must not be retrofitted to flammable refrigerants [10], and a change of refrigerant can affect warranty and insurance [8].
Safety note
Refrigerant work in Australia needs an ARC licence
- Anyone who handles refrigerant, or works on equipment in a way that risks releasing it, must hold an ARC refrigerant handling licence, the ARCtick [9].
- The licence covers the fluorocarbon refrigerants: CFCs, HCFCs and HFCs, including blends that contain them. Handling them without a licence is an offence [8][9].
- Natural refrigerants (CO₂, hydrocarbons, ammonia) are not covered by the ARC scheme, but state work health and safety rules and other licensing can still apply [8][10].
- Never top up, swap or “drop in” a different refrigerant yourself. Check the label on your unit for the refrigerant it was built for, and leave the rest to a licensed technician.
You can check a technician on the ARC website (opens in a new tab). Want to know more about how we work? See why choose us, or read about energy efficiency. Technicians can read the AIRAH Flammable Refrigerants Safety Guide (opens in a new tab).
Where the facts come from
Sources
Figures last checked against these pages on 27 November 2026. Numbers in square brackets in the text match this list. Some Government pages are moving to the new National Environmental Protection Agency website, so links may redirect.
- IPCC. Fourth Assessment Report, Working Group I, Chapter 2, Table 2.14 (with errata): direct 100-year GWPs (opens in a new tab) Science. Used for: AR4 GWP of R11, R12, R22, R32, R125, R134a, R143a.
- IPCC. Fifth Assessment Report, Working Group I, Chapter 8, Appendix 8.A, Table 8.A.1 (opens in a new tab) Science. Used for: AR5 GWP for single gases; HFO atmospheric lifetimes.
- DCCEEW (Australian Government). Hydrofluorocarbon refrigerants: global warming potential values and safety classifications (opens in a new tab) Government. Used for: AR4 GWP and safety class of HFCs, blends, HFOs and natural refrigerants; why Australia uses AR4; what the safety classes mean.
- DCCEEW (Australian Government). HFC phase-down: frequently asked questions (opens in a new tab) Government. Used for: Phase-down schedule, 85% end point, what is and is not covered.
- DCCEEW (Australian Government). Hydrofluorocarbon (HFC) phase-down (opens in a new tab) Government. Used for: Scope of the phase-down: bulk imports only, existing equipment not affected.
- DCCEEW (Australian Government). Montreal Protocol on Substances that Deplete the Ozone Layer (opens in a new tab) Government. Used for: Phase-out dates for CFCs and HCFCs, HFC phase-down steps, Australia ahead of schedule.
- DCCEEW (Australian Government). Controlled substances licence for hydrochlorofluorocarbons (HCFCs) (opens in a new tab) Government. Used for: Australia’s HCFC import limits (zero from 2030) and servicing-only rule from 1 January 2020.
- DCCEEW (Australian Government). Safety considerations when using flammable refrigerants (opens in a new tab) Government. Used for: Flammable refrigerant safety, licensing for fluorocarbon refrigerants.
- Australian Refrigeration Council (ARC). Refrigerant Handling Licence: who needs one and what it covers (opens in a new tab) Licensing body. Used for: ARCtick licence scope and offence for handling without one.
- Australian Refrigeration Council (ARC). Alternative Refrigerants: FAQs (fact sheet ARC5700, 2026) (opens in a new tab) Licensing body. Used for: Natural refrigerants outside the ARC scheme; no retrofitting A1 systems to flammable refrigerants.
- UNEP Ozone Secretariat. Montreal Protocol, Annex A: controlled substances (CFCs) (opens in a new tab) United Nations. Used for: ODP and GWP of CFC-11, CFC-12, CFC-115.
- UNEP Ozone Secretariat. Montreal Protocol, Annex C: controlled substances (HCFCs) (opens in a new tab) United Nations. Used for: ODP and GWP of HCFC-22.
- UNEP Ozone Secretariat. Lists of substances and blends (opens in a new tab) United Nations. Used for: R502 composition and ODP; GWP of HFC blends from components.
- UNEP Ozone Secretariat. The Kigali Amendment (2016) to the Montreal Protocol (opens in a new tab) United Nations. Used for: Kigali Amendment text and entry into force.
- UNEP Ozone Secretariat. Ozone timeline (opens in a new tab) United Nations. Used for: Dates: 1974 discovery, 1985, 1987, 1989, 2007, 2016, 2019; estimated climate benefit of Kigali.
- ASHRAE. Handbook—Fundamentals (2025), Chapter 29: Refrigerants (Tables 1 to 4) (opens in a new tab) Standards body. Used for: Safety groups of R11, R12, R22 and R502; R502 GWP on the Montreal Protocol (AR4) basis; CO₂ critical point.
- ASHRAE. ANSI/ASHRAE Standard 34: refrigerant designations and safety classifications (opens in a new tab) Standards body. Used for: Refrigerant numbering and blend compositions (e.g. R502 = R22/R115 48.8/51.2).
- NIST authors (McLinden, Brown, Brignoli, Kazakov, Domanski). (R)Evolution of Refrigerants, Journal of Chemical & Engineering Data, 2020 (opens in a new tab) Science. Used for: History: early refrigerants, CFCs 1931, R22 1936, HFC replacements, HFOs, Kigali.
- J. M. Calm. The next generation of refrigerants: historical review, considerations, and outlook, International Journal of Refrigeration, 2008 (opens in a new tab) Science. Used for: The four refrigerant generations; R12 commercial from 1931; ammonia in large industrial systems.
- Australian Government. Ozone Protection and Synthetic Greenhouse Gas Management Act 1989 (opens in a new tab) Legislation. Used for: The Act that runs the phase-down and licensing.
- Australian Government. Ozone Protection and Synthetic Greenhouse Gas Management Regulations 1995 (section 42, HFC industry limit) (opens in a new tab) Legislation. Used for: Legislated HFC industry limits by period.
- AIRAH. Flammable Refrigerants Safety Guide (opens in a new tab) Industry body. Used for: Further reading on A2L, A2 and A3 refrigerants for technicians.
- Refrigerants Australia. Refrigerant Update 2025 (opens in a new tab) Industry body. Used for: Transition areas (R32 splits, R1234yf cars, R448A/R449A for R404A); why quota is counted in CO₂-equivalent.